領域 | 默認值 | 描述 |
---|---|---|
Valve Gain Near High Limit [t/v] (接近高限時閥門增益) | 1.0 | 在接近閥門高限時的閥位-設定點增益值。SMOCPro在計算中使用該值計算高低限(見下文)赐写。 ? SPC: 對于正作用控制器(增加控制器的設定值時自動增加閥位)躏吊,增益必須為正。對于反作用控制器(增加控制器的設定值時自動減小閥位),增益必須為負。? DDC: 必須設定為1.0; ? 對正作用控制器: |
Valve Gain Near Low Limit [t/v] (接近低限時閥門增益) | 1.0 | 在接近閥門低限時的閥位-設定點增益值蔬蕊。其用于在計算中使用此值計算高低限(見下文)。? SPC: 對于正作用控制器(增加控制器的設定值時自動增加閥位)哥谷,增益必須為正岸夯。對于反作用控制器(增加控制器的設定值時自動減小閥位),增益必須為負们妥。? DDC: 必須設定為1.0猜扮;?對正作用控制器: |
Feed forward [t/v] (前饋) | True | 此標簽(True/False)用于指示當MV是INACTIVE時此MV的Setpoint Readback(設定點回讀)是否用于抑制前饋干擾旅赢。 |
Setpoint High Limit [t/v] (設定值上限) | 10000000.0 | DDC: 必須與閥門上限相同。 |
Setpoint Low Limit [t/v] (設定值下限) | -10000000.0 | 寫入MV輸出位號值的最低限惑惶。 DDC: 必須與閥門下限相同煮盼。 |
Setpoint High Entry Limit [t/v](設定點輸入高限) | 10000000.0 | 該值定義了允許定義SetPoint High的最高值。 |
Setpoint Low Entry Limit [t/v] (設定點輸入低限) | -10000000.0 | 該值定義了允許定義SetPoint Low的最低值带污。 |
Valve High Limit [t/v] (閥位高限) | 100.0 | 閥位高限僵控。這是SMOCPro用于計算內部設定點限制的。 不論控制器是正作用還是反作用鱼冀,Valve High Limit 必須大于Valve Low Limit报破。 |
Valve Low Limit [t/v](閥位低限) | 0.0 | 閥位低限悠就。這是SMOCPro用于計算內部設定點限制的。 不論控制器是正作用還是反作用充易,Valve Low Limit必須小于Valve High Limit梗脾。 |
Essential For Control [t/v] (重要控制) | False | 此標簽(True/False)用于指示此MV對其子控制器(見Max Time Off Control)的正常運行(ACTIVE)是否是必不可少的。 |
原文:
Field | Default Value | Description |
---|---|---|
Valve Gain Near High Limit [t/v] | 1.0 | Value of the valve-to-setpoint gain near the Valve High Limit. SMOCPro uses this value in the calculations of the Calculated High and Low Limits (see below). ? SPC: For direct acting controllers (increasing the setpoint with the controller in automatic increases the valve position), the gain must be positive. For reverse acting controllers (increasing the setpoint with the controller in automatic decreases the valve position), the gain must be negative. ? DDC: Must be set to 1.0 ? For direct acting controllers: ? For reverse acting controllers: IMPORTANT NOTE: Please refer to the section below entitled “Discussion about the Valve Gain Near High- and Low Limits—dSPdV” for a more complete discussion and explanation regarding these concepts. Our recommendations are also given in this section. |
Valve Gain Near Low Limit [t/v] | 1.0 | Value of the valve-to-setpoint gain near the Valve Low Limit. This is used in the calculations of Calculated High Limit and Calculated Low Limit (see below).? SPC: For direct acting controllers (increasing the setpoint with the controller in automatic increases the valve position), the gain must be positive. For reverse acting controllers (increasing the setpoint with the controller in automatic decreases the valve position), the gain must be negative. ? DDC: Must be set to 1.0 ? For direct acting controllers: ? For reverse acting controllers: IMPORTANT NOTE: Please refer to the section below entitled “Discussion about the Valve Gain Near High- and Low Limits—dSPdV” for a more complete discussion and explanation regarding these concepts. Our recommendations are also given in this section. |
Feed forward [t/v] | True | Flag (True/False) to indicate whether the Setpoint Readback of this MV should be used for feed forward disturbance rejection when the MV is INACTIVE. |
Setpoint High Limit [t/v] | 10000000.0 | DDC: Must be identical to Valve High Limit. |
Setpoint Low Limit [t/v] | -10000000.0 | Minimum limit for the value written to the MV Output Tag. DDC: Must be identical to Valve Low Limit. |
Setpoint High Entry Limit [t/v] | 10000000.0 | This value defines the highest value allowed for SetPoint High. |
Setpoint Low Entry Limit [t/v] | -10000000.0 | This value defines the lowest value allowed for SetPoint Low. |
Valve High Limit [t/v] | 100.0 | High limit for the Valve Position. This is used in SMOCPro to calculate internal setpoint limits. Valve High Limit must be greater than Valve Low Limit, regardless of whether the controller is direct or reverse acting. |
Valve Low Limit [t/v] | 0.0 | Low limit for the Valve Position. This is used in SMOCPro to calculate internal setpoint limits. Valve Low Limit must be less than Valve High Limit, regardless of whether the controller is direct or reverse acting. |
Essential For Control [t/v] | False | Flag (True/False) to indicate if this MV is essential for the continued (ACTIVE) operation of its sub-controller (see Max Time Off Control). |
2016.6.26