| ** Setpoint High Limit(設(shè)定點高限)| MV Set point 高限設(shè)定元莫;缺省值 = 10000 | R/W| R/W|
| ** Setpoint Low Limit(設(shè)定點低限)| MV Set point低限設(shè)定; 缺省值 = 0| R/W | R/W|
| Calc High Constraint(計算高約束) | 該Exasmoc MV的高設(shè)定點限制;| R | R|
| Calc Low Constraint(計算低約束)| 該Exasmoc MV的低設(shè)定點限制;| R | R|
|** SP High Entry Limit(SP高輸入限制)| Setpoint High limit的上限值;SETPOINT HIGH LIMIT <= SP High Entry Limit 肠缔。| R |R/W|
|** SP Low Entry Limit(SP低輸入限制)| Setpoint High limit的下限值;SETPOINT LOW LIMIT >= SP Low Entry Limit。| R| R/W|
|**** SPRB Precision Tolerance(SPRB精度公差)| 包含了當前setpoint readback(設(shè)定點回讀值)和SMOC在上次執(zhí)行時寫入的設(shè)定值之間的最大允許偏差的絕對值陡鹃,然后SMOC使用讀取的當前設(shè)定值作為參考點來計算下一步動作。生成消息151抖坪。SPRB Precision Tolerance應(yīng)等于或小于SPRB Error Tolerance萍鲸。 默認值為(0.1 最大步幅)。| R| R/W|
|**** SPRB Error Tolerance(SPRB誤差公差) |包含了當前setpoint readback(設(shè)定點回讀)值和SMOC在上一次執(zhí)行時寫入的設(shè)定值之間的最大允許偏差的絕對值擦俐,然后SMOC標記一個readback(回讀)錯誤脊阴。控制模式變?yōu)镾tandby(掛起)且生成消息152。 為了在錯誤復(fù)位后返回控制模式嘿期,請再次將所需狀態(tài)打為Standby(掛起)和Control(控制)品擎。SPRB Precision Error Tolerance (SPRB精度誤差公差)應(yīng)等于或小于SPRB Error Tolerance (SPRB誤差公差)。 默認值為(1.1 MV 最大步幅)秽五。| R |R/W|
|Essential for Control(控制必要性) |當MV對控制是必須的時孽查,選擇TRUE。 當MV對控制不是必須的時坦喘,選擇FALSE盲再。選擇TRUE將有以下效果。如果該Exasmoc MV為不可用的情況瓣铣,則Execute Control程序?qū)⒆詣影袳xasmoc控制器置于STANDBY模式答朋。| R |R/W|
|Maximum Time Off Control(最大關(guān)閉控制時間)| 如果Essential of Control is true(控制必要性是True)且Exasmoc MV為不可用狀態(tài),則在Exasmoc將Control模式切換為STANDBY模式之前的最大等待時間棠笑。| R| R/W|
|Valve Position(閥位) |此Exasmoc MV所屬的DCS控制器的MV值梦碗。| R| R|
|Valve High Limit(閥位高限)| 控制閥位高限設(shè)定值;Default = 100 |R |R/W|
|Valve Low Limit(閥位低限)| 控制閥位低限設(shè)定值蓖救;Default = 0| R| R/W|
|Valve Gain Near High(閥位增益高限) |Exasmoc MV控制閥位階躍后的增益高限洪规;Default = 1| -| R/W|
|*Valve Gain Near Low(閥位增益低限)| Exasmoc MV控制閥位階躍后的增益低限;Default = 1 |- |R/W|
|Calculated Move(計算動作)| 每次執(zhí)行控制周期時由Exasmoc控制操作計算的增量值循捺。若Exasmoc處于OFF或 STANDBY模式斩例,則該值為0。 | R |R|
|Calculated MV(計算MV)| 每次執(zhí)行控制周期時由Exasmoc控制操作計算的絕對值从橘。若Exasmoc處于OFF或 STANDBY模式念赶,則該值被凍結(jié)。| R| R|
原文:
| | | | |
| ------------- |:-------------:| -----:|
| ** Setpoint High Limit | MV Set point high limit setting. Default = 10000| R/W| R/W|
| ** Setpoint Low Limit | MV Set point low limit setting. Default = 0| R/W | R/W|
| Calc High Constraint | High set point limit of this Exasmoc MV| R | R|
| Calc Low Constraint | Low set point limit of this Exasmoc MV | R | R|
| ** SP High Entry Limit | The upper bound value of Setpoint High limit. SETPOINT HIGH LIMIT <= SP High Entry Limit should be filled.| R | R/W|
| ** SP Low Entry Limit | The lower bound value of Setpoint High limit. SETPOINT LOW LIMIT >= SP Low Entry Limit should be filled.| R | R/W|
| **** SPRB Precision Tolerance| Contains the absolute value of the maximum allowable discrepancy between the current setpoint readback value and the setpoint value written by SMOC at the previous execution before SMOC uses the current setpoint read as the reference point to calculate the next move. Message 151 is generated. SPRB Precision Tolerance should be equal or smaller than SPRB Error Tolerance. The default value is (0.1of MV maximum move size) | R | R/W|
| **** SPRB Error Tolerance| Contains the absolute value of the maximum allowable discrepancy between the current setpoint readback value and the setpoint value written by SMOC at the previous execution before SMOC flag a readback error. The control mode becomes Standby and Message 152 is generated. In order to return to Control mode after the error is reset, turn on Desired Status from Standby and Control again. SPRB Precision Error Tolerance should be equal or smaller than SPRB Error Tolerance. The default value is (1.1 MV maximum move size).| R| R/W|
| Essential for Control| TRUE- is selected when MV is essential for control. FALSE -(Default) is selected when MV is not essential for control. Selection of ¨TRUE〃 provides following effect. If in case Exasmoc MV is not available then ¨Execute Control〃 routine will automatically put Exasmoc controller into STANDBY mode. | R | R/W|
| Maximum Time Off Control | Maximum time specified to hold Exasmoc in Control mode before switching over to STANDBY mode if ¨ Essential of Control is true〃 and Exasmoc MV are not available. | R | R/W|
| *Valve Position| MV value of DCS controller to which this Exasmoc MV belongs. | R | R|
| *Valve High Limit| Control Valve high limit setting Default = 100 | R| R/W|
| *Valve Low Limit| Control Valve low limit setting. Default = 0 | R| R/W|
| *Valve Gain Near High| High limit of Gain in the Exasmoc MV measurement to a change in the Control Valve position. Default = 1 | - | R/W|
| *Valve Gain Near Low| Low limit of Gain in the Exasmoc MV measurement to a change in the Control Valve position. Default = 1 | - | R/W|
| Calculated Move | Incremental value computed by Exasmoc control action per execution of control period. If Exasmoc is in OFF or STANDBY mode then this value is zero. | R| R|
| Calculated MV| Absolute value computed by Exasmoc control action per execution of control period. If Exasmoc is in OFF or STANDBY mode then this value freezes. | R | R|